Product overview
The 630A European rear connector can be connected to the European front connector or another rear connector to provide an extended cable connection loop (branch). It cannot be directly connected to the casing seat and wall bushing. The tail can be directly blocked with an insulating plug, and can also be extended to connect another European rear connector or rear arrester.
12kV cable model configuration table
Model specifications |
Adapt to main insulation outer diameter (mm) |
Adapt to cable section (mm²) |
ZRQ3-12/630-25 |
16.5-17.8 |
25 |
ZRQ3-12/630-35-50 |
17.0-20.0 |
35-50 |
ZRQ3-12/630-70-95 |
20.0-23.1 |
70-95 |
ZRQ3-12/630-120-150 |
23.1-26.1 |
120-150 |
ZRQ3-12/630-185-240 |
25.8-30.8 |
185-240 |
ZRQ3-12/630-300 |
30.4-32.3 |
300 |
ZRQ3-12/630-400 |
33.0-35.4 |
400 |
24kV cable model configuration table
Stress body specification |
Adapt to main insulation outer diameter (mm) |
Cable type 12/20kV |
Cable type 18/20kV |
16. |
19.6-20.9 |
35-50 |
|
19. |
22.4-25.5 |
70-120 |
35 |
23. |
26.3-29.5 |
150-185 |
50-95 |
26. |
30.9-34 |
240-300 |
120-185 |
31. |
36.1-39.5 |
400-500 |
240-300 |
35. |
41.5-45 |
630 |
400-500 |
Performance
● Provide fully shielded and fully sealed separable connections when mated with a suitable sleeve or plug; long-term operation under water and other harsh conditions;
● Built-in capacitance test point is used to determine the live state of the line or install a live indicator; there is no minimum safety distance requirement between phases;
● The installation can be vertical, horizontal or any angle.